- Highly sensitive, false alarm-proof smoke detection for mid-sized areas
- High Power Light Source technology allows normal to extremely high sensitivity
- Maximum security against false alarms thanks to LOGIC·SENS
- PIPE·GUARD patented air flow monitoring
- Detector module with response sensitivity of up to 0.015 % obs./m, 0.1 % obs./m or 0.5 % obs./m
- Monitors areas up to 3,200 m² in size; max. pipe length of 2 x 160 m with up to 2 x 20 aspirating points
- Precise air flow monitoring within measuring chamber ensures maximum operational reliability
- Low operating costs thanks to extremely low power consumption (as low as 140 mA, depending on device type)
- Optional alarm system with adjustable pre-alarm
- Plug-and-play system for easy planning and installation
- Range of DIN EN 54-20/ISO 7240-20 certified accessories
- Operating temperature range: -30 °C to +60 °C (SILENT version: 0 °C to +40 °C)
- Usable in very dusty environments thanks to (optional) filter concept
- SILENT version (23 dB(A) and up) for noise-critical areas